Smoke spreading characteristics during a fire in a shallow urban road tunnel with roof openings under a longitudinal external wind blowing

Publication date: June 2017
Source:Fire Safety Journal, Volume 90
Author(s): Futoshi Tanaka, Nobuyoshi Kawabata, Fumiaki Ura
A series of fire experiments was conducted using a 1:12 scale model of a shallow urban road tunnel with roof openings to clarify the flow structure of smoke and fresh air during a fire with a longitudinal external wind blowing above the roof openings. The model tunnel consisted of two road tubes separated by a pillar-type median structure. Five fire test cases were conducted by changing the heat release rate as the experimental parameter. When the smoke produced by a fire in the tunnel tube was exhausted by natural ventilation through the roof openings of the tunnel tube, fresh air was sucked in from the roof openings of the opposite tunnel tube. The flow of exhausted smoke and sucked-in fresh air created a complex three-dimensional flow structure inside the tunnel tubes. Stratified smoke that had formed under the ceiling of the tunnel tube was disturbed by the flow of sucked-in fresh air and was diffused on the upstream side of the fire. Compared to the condition without a longitudinal external wind, when a longitudinal external wind blew over the tunnel with the pillar median structure, the smoke spreading distance on the upstream side was longer than that without the external wind due to the diffusion of smoke. On the other hand, the smoke spreading distance on the downstream side of the fire was shorter than that without the external wind due to the improved smoke extraction performance by the Venturi effect of the longitudinal external wind. Furthermore, the smoke spreading distance on the downstream side was nearly constant and independent of the heat release rate of the fire, within the scope of our experimental conditions.



http://ift.tt/2pgxefY

Δεν υπάρχουν σχόλια:

Δημοσίευση σχολίου